Westerm D20K: Settings - GE D20 Installation And Operation Manual

Hide thumbs Also See for D20:
Table of Contents

Advertisement

D20/D200
Installation and Operations Guide
Connections and Configuration
WESTERM
The following table gives jumper settings for Z2 to Z39.
D20K: Settings
Jumper
Jumper
Jumper
Number
Position
Setting
Z2 & Z3
1 – 2
2 – 3
Z8
1 – 2
2 – 3
Z9
1 – 2
2 – 3
Z14
1 – 2
2 – 3
Z15
1 – 2
2 – 3
Jumper
Jumper
Number
Position
Z5 – Z7
1 – 2 & 3 – 4
Z19 – Z21
1 – 2
Z30 & Z31
2 – 3
Z4, Z10,
1 – 2 & 3 – 4
Z11, Z18,
1 – 2
Z22, Z29,
Z32, Z33
2 – 3
Z12, Z13,
1 – 2 & 3 – 4
Z23, Z24,
1 – 2
Z25, Z34,
Z35, Z36
2 – 3
Z16, Z17,
1 – 2 & 3 – 4
Z26, Z27,
1 – 2
Z28, Z37,
Z38, Z39
2 – 3
70
, continued
Option
1A
1B
1C
IN
IN
Option
2A
2B
2C
IN
IN
IN
IN
IN
IN
IN
IN
Jumper
Option
Setting
3A
3B
3C
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
994-0078-2.00-7
Jumper Definition
Control O/P Source = D20 Peripheral DC Supply Voltage
Control O/P Source = External Source Supplied to TB1 – 1 & 54
T/C Configuration for Control O/P 1 – 8 = (T/C 1 – 8)
R/L Configuration for Control O/P 1 – 8 = (R/L 13 – 16)
T/C Configuration for Control O/P 9 – 16 = (T/C 9 – 16)
R/L Configuration for Control O/P 9 – 16 = (R/L 9 – 12)
T/C Configuration for Control O/P 17 – 24 = (T/C 17 – 24)
R/L Configuration for Control O/P 17 – 24 = (R/L 5 – 8)
T/C Configuration for Control O/P 25 – 32= (T/C 25 – 32)
R/L Configuration for Control O/P 25 – 32 = (R/L 1 – 4)
Jumper Definition
3D
T/C Configuration (T/C 1 – 8)
R/L Configuration (R/L 13 – 16)
Form C or Open Collector Control Outputs 1 – 8
T/C Configuration (T/C 9 – 16)
R/L Configuration (R/L 9 – 12)
Form C or Open Collector Control Outputs 9 – 16
T/C Configuration (T/C 17 – 24)
R/L Configuration (R/L 5 – 8)
Form C or Open Collector Control Outputs 17 – 24
T/C Configuration (T/C 25 – 32)
R/L Configuration (R/L 1 – 4)
Form C or Open Collector Control Outputs 25 – 32