D20Me/Me Ii Power Connections; D200 Power Supply; Procedure - GE D20 Installation And Operation Manual

Hide thumbs Also See for D20:
Table of Contents

Advertisement

GE Energy
Connections and Configuration
D20ME/ME II
Power is supplied to the D20ME/ME II Main Boards through the backplane:
Power
WESTERM D20M+ SS for non-VME. See Module Layout 517-0224-ML
Connections
WESTERM D20 VME bus backplane. See Module Layout 517-0123-ML
SCHROFF VME bus backplane. See Module Layout 500-0307-ML
D200 Power
The D200 uses two power supply units, one for 5V and one for +12/-12V supply.
Supply
Power is supplied through the CCU Switch and Fuse Assembly. Each unit can be
switched to accommodate 110V or 220V mains power supply. There is also a
version with a 48 VDC input.
There may be two of each power supply for redundancy: two 5V and two +12/-12V.

Procedure

To replace a 5V power supply:
Step
1
2
General
Full
, continued
Remove the 5V Power Supply from the D200 Chassis.
Inspect the right side of the casing.
Note:
In the middle of the right side a slotted dial is visible through
one of the casing apertures. This dial indicates the mains
supply voltage setting: 115V or 220V.
Set the voltage by carefully inserting a small screwdriver through the
aperture to turn the dial approximately 45°.
Result:
The mains power supply rating has been set for the Power
Supply.
994-0078-2.00-7
Installation and Operations Guide
Action
D20/D200
51