Electrical installation
1
Electrical installation
ID no.: 1400.201B.5-00
mounting the mains filter on a metal, conductive and well-grounded base plate and
the connecting the cable shield to the backing plate as close as possible to the "Load"
connection on the mains filter.
This cable can also be unshielded up to a cable length of max. 0.3 m.
4.6.1
Layout, underside X7 and X8
X7
X8
Figure 4.8
Layout, BG1 (underside)
Date: 02/2020
X7
X8
Figure 4.9
Layout, BG2 (underside)
Operation Manual Supply Unit SO CM-P BG1+2
4.6.2
Connector specification
Term.
Specification X8 BG1
L3
x 3 x 230 V AC
x 3 x 400-480 V AC
L2
x Approx. 3 x 25 A current
L1
consumption
L3
x Connection cross-section:
6 mm
2
max.
L2
x Shield lug on the connector is
L1
only for the connection of the
cable shield (see photograph).
For ordering information on
the connector set, see note.
Table 4.4
Specification, AC mains connection X8 BG1
Term.
Specification X8 BG2
L3
x 3 x 400-480 V AC
L2
x Approx. 3 x 50 A current
consumption
L1
x Connection cross-section:
16 mm
max.
2
x Shield lug on the connector is
only for the connection of the
cable shield (see photograph).
L1
For ordering information on
the connector set, see note.
Table 4.5
Specification, AC mains connection X8 BG2
28
X8
X8
L2
L3