Modbus function codes
Code
Command
04h
Read n Words
05h
Write 1 Bit
06h
Write 1 Word
0Fh
Write n Bits
10h
Write n Words
16h
Mask 1 Word
17h
Write n Words and Read m
Words
Respond of the coupler
70
Description
Read n words master input area 3x
Write 1 bit to master output area 0x
Write 1 word to master output area 4x
Write n bits to master area 0x
Write n words to master area 4x
Mask 1 word in master output area 4x
Write n words into master output area 4x and the respond contains m
read words of the master input area 3x
Byte sequence in a word
High byte
If the slave announces an error, the function code is sent back with a "OR" and 80h.
Without an error, the function code is sent back.
Coupler answer:
Function code OR 80h
Function code
If the slave announces an error, the function code is sent back with a "OR" and 80h.
Without an error, the function code is sent back.
01h: Function number is not supported
02h: Addressing errors
03h: Data errors
04h: System SLIO bus is not initialized
07h: General error
1 word
Low byte
® Error & error number
® OK