Access to the Ethernet coupler > Web server
Tab: Parameter
Parameter
Data type
Link monitoring
BOOL
Communication
UINT_32
timeout [ms]
IO cycle [µs]
UINT_32
Tab: Diagnosis
Tab: Security
Tab: IP
54
Here you can change the current parameters of the IM 053MT.
To change the parameters, the IM 053MT should be in BASP status.
Area
TRUE/FALSE
n
0 ... 30000
n
0
n
1000
n
2000
n
4000
n
8000
10000
n
n
Link monitoring
As soon as both Ethernet cables are pulled with enabled Link monitoring, the
communication is finished by the IM 053MT, BASP (Befehls-Ausgabe-Sperre, i.e.
command output disable) is activated and this is indicated with flashing SB LED.
Link monitoring reacts only when both Ethernet cables are pulled.
n
Communication timeout
At Communication Timeout [ms] you can specify a timeout value for Ethernet
communication in ms.
If there is no Modbus/TCP communication for the specified time, BASP is set on
the System SLIO bus.
With the value 0, you can deactivate the time monitoring.
n
IO cycle
With IO cycle, you can specify the cycle for the System SLIO bus within which the
I/O image is to be refreshed.
With the value 0 you can set the maximum possible cycle time (no delay).
n
Configuration State
Deviations between the setpoint and actual configuration are shown here
(OK: no deviation).
n
Diagnosis Entries
Here all pending diagnostic messages are shown.
n
Diagnosis Buffer
Here the content of the diagnostics buffer is listed.
All functions for the writing access to the Ethernet coupler can be secured by a password.
Here you may assign to your Ethernet coupler IP address data. For valid IP address data
please contact your system administrator.
Default value
Description
FALSE
Link monitoring Ethernet
0
Timeout Ethernet communication
1000
System SLIO bus cycle
HB300 | IM | 053-1MT01 | en | 19-40