Deployment
Access to the Ethernet coupler > Web server
56
n
Activate Commissioning mode
With [Activate], the Ethernet coupler enters the Commissioning state.
- When changing to the "Commissioning" state, all outputs are reset.
- BASP (Befehlsausgabesperre i.e. command output disable) is not activated, i.e.
all module outputs can be controlled and the inputs can be read.
In the Commissioning state you have the following options:
- Outputs can be set via the web page in the 'Data' tab of the selected module.
- Parameters can be written via the web page in the 'Parameter' tab of the
selected module.
- You can perform a firmware update.
With [Deactivate] you leave the Commissioning state
- When leaving Commissioning all outputs are reset.
- BASP is activated, i.e. all module outputs are switched off and the inputs are not
read.
CAUTION!
Please consider that controlling of output values represents a poten-
tially dangerous condition.
As long as Commissioning state is activated, set variables retain their
value.
Commissioning state should only be used for test purposes respec-
tively for troubleshooting.
n
Export Station Configuration
With [Save] a window is opened and shows the configuration as XML. Select 'File
è Safe as' and safe the current configuration as XML file.
Import Station and Modules Configuration
n
Select with [Search...] the according XML file and load this with [Load]. While loading
the parameters of the IM 053MT and the modules are loaded.
n
Import Modules Configuration
Select with [Search...] the according XML file and load this with [Load]. While loading
only the parameters of the modules are loaded. The parameters of the IM 053MT fur-
ther exist.
n
Save Configuration of all Modules
With [Save] the current configuration is stored in the IM 053MT. If the current module
ID deviates from the just configured module ID of the stored configuration of the IM
053MT after a system start-up, the IM 053MT does not go into RUN and shows the
error on its web server.
n
Delete Configuration of all Modules
With [Delete] the configuration in the IM 053MT may be deleted.
Only there is a configuration for a module, this may be used to check
preset and current configuration. If the current configuration differs from
the preset (e.g. module was removed) the system reports an error and
does not go to RUN. If there is no preset module configuration and the
current configuration is changed during operation, the IM 053MT per-
forms a restart and switches again to RUN.