3 Checking and starting the operation
3-4 Operations using the LCD menu
☆: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Settings Boot Settings
88
Menu
Description
Auto Reboot
Selects whether to perform
automatic reboot from power
outage.
Cold Start
Selects whether to enable
the "Cold Start" function,
which can start up the UPS
without "AC input".
Reboot Delay
Sets the delay time for
Time
recovery from a power
outage.
Load
The time to start the output
Segments(B)
of "power supply output"
ON
group B can be delayed.
Load
The time to stop the output of
Segments(B)
"power supply output" group
OFF
B can be accelerated.
Load
The time to start the output
Segments(C)
of "power supply output"
ON
group C can be delayed.
Load
The time to stop the output of
Segments(C)
"power supply output" group
OFF
C can be accelerated.
Value
Automatic restart:
Enabled (factory default), Disabled
Enable, Disable (factory default)
Reboot delay time:
0 to 999 seconds
(Factory default: 9 seconds)
ON delay: 0 to 9 seconds
ON delay: 0.0 to 0.9 minutes
ON delay: 0 to 30 minutes
(Factory default: 0 seconds)
(Note 3)
OFF delay: 0 to 9 seconds
OFF delay: 0.0 to 0.9 minutes
OFF delay: 0 to 30 minutes
(Factory default: 0 seconds)
(Note 3)
ON delay: 0 to 9 seconds
ON delay: 0.0 to 0.9 minutes
ON delay: 0 to 30 minutes
(Factory default: 0 seconds)
(Note 3)
OFF delay: 0 to 9 seconds
OFF delay: 0.0 to 0.9 minutes
OFF delay: 0 to 30 minutes
(Factory default: 0 seconds)
(Note 3)
BU5002R/BU3002R/BU3002RH
Menu type
Standard
Advanced