Omron BU5002R Instruction Manual page 125

Ups/200 to 240 v
Table of Contents

Advertisement

Problem
Buzzer
Output Charge
• The UPS
None
OFF
power
does not
turn ON.
None
OFF
• There is no
power
output to
the
secondary
side
(connected
devices
side)
• There is no
response
None
OFF
when the
power
switch is
pressed
None
OFF
None
OFF
Backup is not
None
ON
possible
BU5002R/BU3002R/BU3002RH
Message
displayed on
LCD (Note 2)
OFF/Dis
OFF
The AC power supply is
chargin
not input to the UPS.
g
When the "AC input
OFF/Dis
OFF
overcurrent protection" is
chargin
g
activated, the connected
devices may be too
many, or a short circuit is
occurring on the
connected devices side.
ON
Stand by
Charging is insufficient,
Bat.level
so it is not possible to
start up.
ON
AC I/P
The input voltage or
abnormal-VH
frequency is low or high.
AC I/P
abnormal-VL
AC I/P
abnormal-FH
AC I/P
abnormal-FL
ON
Stand by
There is a short circuit on
RemoteOFF
the remote ON/OFF
terminal, or the LCD
menu "Remote ON/OFF
Logic" has been changed
to "OFF when opened".
ON
bE
Charging is insufficient.
Battery Empty
8 Troubleshooting
Cause
Check if there is any problem on
the power supply to which the AC
input cable is connected.
Disconnect all the connected
devices, separate the input power
supply, turn ON the circuit breaker,
reconnect the input power supply,
and turn ON the power switch of
the UPS again. If the normal "status
display" does not appear even if
doing the above, it is judged as a
failure. If the unit is in the normal
state, check the connected
devices.
Lower the value in [3.Settings] -
[Boot Settings] - [Reboot
Batt.level]. When set to 0%, the
battery charging level is not
included in the boot conditions, and
booting is immediate.
Check the voltage and frequency of
the input power from
[1.Measurements] - [Input/Output
Meter].
See "6 Contact signal".
Connect the UPS to the
commercial power supply, and
charge the batteries for 8 hours or
more. If expansion battery units are
connected, more charging time is
required. (24 hours when 1
expansion unit is connected, 40
hours when 2 are connected, and
56 hours when 3 are connected)
Action
125