Omron BU5002R Instruction Manual page 124

Ups/200 to 240 v
Table of Contents

Advertisement

8 Troubleshooting
Problem
Buzzer
Buzzer
Continuo
sounds
us sound
continuously
Continuo
us sound
Continuo
us sound
Continuo
us sound
Continuo
us sound
Continuo
us sound
Continuo
us sound
Continuo
us sound
Continuo
us sound
124
Message
Output Charge
displayed on
LCD (Note 2)
OFF
Undefin
Fault-ES
ed (note
Output
3)
short-circuit
ON
Undefin
Fault-EO
ed (note
Overload stop
3)
ON
Undefin
Fault-E1
ed (note
Output over vol.
3)
ON
Undefin
Fault-E2
ed (note
Output under
3)
vol.
ON
Undefin
Fault-E3
ed (note
Batt.Over
3)
Charge
ON
Undefin
Fault-E4
ed (note
Batt.Under
3)
Charge
ON
Undefin
Fault-E6
ed (note
Over
3)
temperature
ON
Undefin
Fault-E7
ed (note
3)
OFF
OFF/dis
Fault-E12
chargin
Battery Over
g
temp
Cause
Output has stopped due
Check whether there is a short
to a short circuit on the
circuit on the AC input of the
connected devices side
connected devices, or whether the
or a major connection
connected capacity is exceeding
capacity overload.
the rated capacity.
The UPS switches to
Turn off the power switches of all
bypass operation
the devices connected to the UPS,
because of overload
and after reducing the connected
(note 1).
devices, turn on the power
switches of the UPS and the
connected devices.
The output voltage is
Turn off the power switches of all
abnormal (high), so the
the devices connected to the UPS,
UPS switches to bypass
and turn on the power switch of the
operation (note 1).
UPS only. If the displayed content
does not change, the UPS is faulty.
The output voltage is
Contact the shop of purchase.
abnormal (low), so the
Note: The output voltage can be
UPS switches to bypass
operation (note 1).
The charging voltage is
abnormal (high), so the
UPS switches to bypass
operation (note 1).
The charging voltage is
abnormal (low), so the
UPS switches to bypass
operation (note 1).
The internal temperature
Check that the ambient
is abnormal, so the UPS
temperature of the UPS is 40°C or
switches to bypass
less. If the UPS is not used in a
operation (note 1).
high temperature environment, the
UPS is faulty. Contact the shop of
purchase.
A breakdown of an
The UPS is faulty, so contact the
internal component or
shop of purchase.
internal circuit has been
detected, so the UPS
switches to bypass
operation. (note 1).
An abnormal battery
The UPS is faulty, so contact the
temperature was
shop of purchase.
detected during backup
operation. Output will
stop.
BU5002R/BU3002R/BU3002RH
Action
checked from the LCD Menu
by "1.Measurements"-
"Input/Output Meter". The
battery voltage can be
checked by
"1.Measurements" - "Battery
Meter".