Omron BU5002R Instruction Manual page 69

Ups/200 to 240 v
Table of Contents

Advertisement

■ Battery error
UPS
Icon
status
Battery
deterior
ation
Battery
end of
life
Battery
temper
ature
error
Battery
discon
nection
Note 1: Varies depending on the operational status.
BU5002R/BU3002R/BU3002RH
3-1 Names and functions of each part of the operation and display sections
Symbol
Buzzer
Intermittent,
at intervals
(Note
of 2 seconds
1)
Intermittent,
at intervals
(Note
(Note
of 2 seconds
1)
1)
Intermittent,
at intervals
(Note
of 4 seconds
1)
Intermittent,
at intervals
(Note
(Note
(Note
of 2 seconds
1)
1)
1)
3 Checking and starting the operation
Text
Output
Charge
displayed
on top
ON
Fault-E10
ON
or
discharging
ON
(Note
Fault-E10
1)
ON
Charging is
(Note
Fault-E12
stopped
1)
ON
Charging is
(Note
Fault-E10
stopped
1)
○: ON, ●: OFF
Description
Solution
The
self-diagnostic
test result
indicates
battery
Replace the
deterioration.
battery.
The battery
reached end
of life.
Charging is
Check that
stopped
the ambient
because the
temperature
battery
of the UPS is
temperature is
40°C or less.
high.
The battery is
Check the
not
battery cable
connected.
connection.
3
69

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bu3002rBu3002rh

Table of Contents