Omron BU5002R Instruction Manual page 14

Ups/200 to 240 v
Table of Contents

Advertisement

Safety precautions
Connect the unit to a power supply outlet (commercial power supply)
with the following current capacity.
BU5002R:
BU3002R/BU3002RH:
⚫ The power supply cable may get hot.
⚫ When devices are connected with the maximum output capacity, the following
maximum current flows.
BU5002R:
BU3002R/BU3002RH:
When you change the input cable, be sure to connect it as prescribed.
Do not carry out any works involving connection of the AC input
terminal of the unit while it is connected to a commercial power supply.
⚫ Cables connected to a terminal block shall satisfy the input current specification of
the unit.
⚫ There is a possibility of an electric shock or electric leakage.
Install this unit only in the specified orientation.
⚫ You may be injured if the product is toppled or dropped.
⚫ If installed in an orientation other than the specified orientation, it is not possible to
protect against battery leakage.
⚫ When installing vertically, be sure to use the stand for vertical layout provided with
the product.
Do not use in locations where the maximum temperature exceeds 40°C.
⚫ The battery may degrade rapidly and cause a fire.
⚫ There is a risk of a breakdown or malfunction of the unit.
Do not connect devices that exceeds the output capacity of the unit.
The connected devices can be expanded using a power outlet strip, etc.,
but in this case do not connect devices that exceeds the current
capacity of the outlet strip.
⚫ The unit will detect an overload and stop output.
⚫ The wiring of the power outlet strip may generate heat and cause fire.
When installing this unit on a rack, install this unit on the lowermost
shelf of the rack.
⚫ You may be injured if the product is dropped.
Remove the battery when moving the unit.
⚫ If not removed, because of the heavy object, there is a risk of injury by dropping the
product, or by the sheer weight of the product.
14
Caution (for installation and connection)
30 A or more
18 A or more
30A
18A
BU5002R/BU3002R/BU3002RH