Uninterruptible Power Supply UPS BU100RS 使用说明书 Instruction Manual BU100RS ・ This manual provides important safety-related information. Thoroughly read and understand this manual before installing and using the product. ・ Keep this manual in a convenient location so that you can refer to it whenever necessary.
Introduction Features of this product Thank you for purchasing Omron's Uninterruptible Power Supply (UPS). ● The UPS protects computers and other devices from power failures, voltage variations, instantaneous voltage drops, and surge voltage such as that caused by lightning (a phenomenon in which extraordinary high voltage occurs instantaneously).
Page 3
Introduction IMPORTANT SAFETY INSTRUCTION 1. SAVE THESE INSTRUCTIONS. This manual contains important instructions for BU100RS that should be followed when using the UPS and batteries. 2. SYMBOL This symbol indicates earth ground. This symbol indicates turning on/off UPS. 3. INTERNAL BATTERY Internal battery voltage is 24VDC for BU100RS.
We recommend charging the UPS before using it. Operate 3. Check and start operation Perform maintenance and inspection Perform maintenance and inspection The battery must 4. Maintenance and Inspection be replaced Replace the battery 4.2 Replacing the battery BU100RS...
3-3-1 Start and stop procedures ....................47 Interpreting beeps and displays ..............49 3-4-1 Displays and beeps in normal operations ................49 3-4-2 Displays and beeps while testing ..................50 3-4-3 Displays and beeps during power failure or AC input error ..........50 BU100RS...
Page 6
6-1-3 Contact signal port (female D-SUB 9 pin) ................81 6-1-4 Remote ON/OFF port ......................81 6-1-5 Contact Signal ratings ......................81 6-1-6 Contact Signal circuit ......................81 6-1-7 Example of the use of the Contact Signal circuit ..............82 BU100RS...
Page 7
6-1-8 Precautions and notes for the use of the Contact Signal ........... 82 7 Troubleshooting ..................83 8 Note of Chinese ..................84 9 References ................... 93 Specifications ....................93 Dimensions ....................94 Battery life ...................... 98 China RoHS Information ................99 BU100RS...
This is a Class A product based on the standard of the VCCI Council. If this equipment is used in a domestic environment, radio interference may occur, in which case, the user may be required to take corrective actions. BU100RS...
Page 9
● If you install the unit in an orientation other than specified, the unit cannot be protected from a battery fluid leakage. Do not use the unit where the maximum temperature exceeds 40°C. ● The battery deteriorates rapidly. ● Doing so may cause a failure or malfunction of the unit. BU100RS...
Page 10
● Failure to do so might cause a tightening error and result in a fire or fall. (Table 1) Specified tightening torque Nominal Type of screw used Tightening torque diameter Ear-bracket mounting flat head screw, 0.55±0.1 N·m terminal-block-cover mounting screw 1.23±0.15 N·m Terminal-block-cable mounting screw 2.75±0.2 N·m Rack mounting screw BU100RS...
Page 11
If fluid (dilute sulfuric acid) leaks from the interior, do not touch the fluid. ● Doing so may cause blindness or burns. ● If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor. BU100RS...
Page 12
Do not insert metal objects into the power supply output receptacle of the UPS. ● Doing so may result in electric shock. Do not insert metal objects into the battery connectors. Do not short between the connector terminals. ● Doing so may result in electric shock. BU100RS...
Page 13
Remove the connection from ground if any part of the battery is determined to be grounded. ● Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. BU100RS...
Page 14
: Déterminer si la pile est mise à la terre. Si elle est mise à la terre, effectuer la deconnection. Le contact avec une pile mise à la terre peut créer un choc électrique. Ceci sera réduit si cette mise à la terre est supprimée pendant installation et maintenance. BU100RS...
Page 15
● This manual contains important safety-related information. Please read and understand the contents of the manual before beginning operation. If this manual is misplaced, download the manual from our website. BU100RS...
Page 16
● Turn OFF the unit’s “Power” switch when storing it. Do not install or store the unit in a place exposed to direct sunlight. ● The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable. BU100RS...
1-2 Checking the contents Check whether all the package contents are included and there is no damage found on their appearance. If you should notice defects or anything wrong, contact us; OMRON Electronic Systems & Equipments Customer Support Center. BU100RS...
Ear brackets (2p) and ear-bracket mounting flat head screws (M3 x 6p) are provided with an optional support angle. < Related products > Replacement Replacement fan Support angles compatible with EIA/JIS battery pack 19-inch racks Vertical floor CD-ROM Optional cable for UPS mounting bracket service BUC26 BU100RS...
For information on the function of each part, refer to “2 Installation and connection” and “3 Check and start operation” that provides the details. ● Front view <BU100RS> (Air vent) (Operation panel) <Enlarged view of the operation panel> A: Status indicator E: “Setting switch”...
Page 20
1 Preparation 1-4 Name of each part ● Rear view <BU100RS> B C D A: Cooling fan (air vent) E: Power supply output receptacles (Backup is performed during power failure.) B: RS232C port F: Input protection C: Contact signal port...
AC100V Inverter Filter (high power Noise input (sine factor filter wave) Input Power converter) overcurrent supply Output protection relay switching Step-up converter Control Power supply Charging circuit switch circuit At startup/capacity exceeded/error Battery During Line mode During Battery mode BU100RS...
The product serial number label is also included. ● Allow sufficient space at the back for the UPS unit and Input power cable, and AC input cables of the connected devices. BU100RS...
Page 23
2 Installation and connection 2-1 Installation <BU100RS> Correct Positions Ba careful not to get your fingers caught when arranging the unit. Note: For vertical installation, be sure to use optional verti- cal floor mounting brackets (Air vents are facing upward) (BAP100R).
To mount to or remove from the rack, secure a space to put your hands in so as to hold the UPS. ● If there is no sufficient space, the UPS cannot be mounted correctly or may fall. BU100RS...
Page 25
● A loose screw may cause damage to the product. If mounting the UPS with both front and rear mount rails, use a 19" rack support angle mounting bracket set (BAP100RS). ● For details about how to mount UPS, refer to the instruction manual for BAP100RS. BU100RS...
Page 26
This section explains how to mount the UPS into a rack for horizontal installation. For details about vertical installation, refer to pages 27 to 29. * If the rack's posts have no female threads, attach rack cage nuts in advance. BU100RS...
Page 27
* This work must be done by two people. Since the front side only is being held, the rear side may slightly tilt downward while tightening the screws. So, hold the UPS with the rear side being lifted so that it becomes level to tighten the screws. BU100RS...
Page 28
This section explains how to mount the UPS into a rack for vertical installation. For details about horizontal installation, refer to pages 25 to 27. * If the rack's posts have no female threads, attach rack cage nuts in advance. BU100RS...
Page 29
* This work must be done by two people. Since the front side only is being held, the rear side may slightly tilt downward while tightening the screws. So, hold the UPS with the rear side being lifted so that it becomes level to tighten the screws. BU100RS...
Page 30
Periodically check that the screws are not loose and that there is no gap between metal sheets. If a gap exists, while holding the whole UPS, tighten the screws again with the specified tightening torque (2.75±0.2N・m). Note: A loose screw may cause damage to the product. Then, the installation process is completed. BU100RS...
For stationary horizontal installation, make sure that this product does not slide or fall. ● Upright installation Fix the brackets (2p) using M3 flat head screws (6p) provided with the product option (model BAP100R) to the UPS with the specified torque (0.55±0.1N・m). BU100RS...
Connect devices you want to back up to the Power Supply Output Receptacles of the UPS. ・ If you need more output receptacles than those of the UPS, purchase a plug strip and use it for extra output receptacles. Computer peripheral devices External HDD BU100RS...
Page 33
See also "5 To perform shutdown processing of the devices when a power failure occurs", and "6 Using the contact signal functions" Note: If you do not use the UPS monitoring software and Contact Signal, this step is not required. BU100RS...
■ Connection procedure Loosen the clamp on the side of the AC input cable, then remove the screws for the terminal block cover and detach the terminal block cover. BU100RS...
Page 35
(AWG16~AWG12) Recommended cable size 2 mm (AWG14) L, N, G Amount of stripped wire 6 to 8 mm Tightening torque 1.23±0.15 N・m Outer diameter of the calbe φ 6 to 10mm Recommended ring terminal for the wire V2-P4 (JST) BU100RS...
Page 36
2 Installation and connection 2-2 Connecting the equipment Fix the terminal block cover with specified torque (0.55±0.1N・m) using screws and turn the clamp to tighten it in place. BU100RS...
● The unit may fail. For other cautions when connecting the UPS, refer to “Caution (for installation and connection)” shown in the “Safety precautions” of the beginning of this manual. Installation and connection is now complete. BU100RS...
If battery replacement is Battery required due to battery replacement is not performance degradation necessary. (including deterioration); if battery voltage significantly drops becomes specified value or lower; if the battery is not connected; or if the battery voltage is lower than 18V. BU100RS...
Page 40
(“Setting” switch 3)... Factory setting: OFF OFF: The self-diagnostic test is automatically executed once every 4 weeks. ON: Does not perform the auto test once every 4 weeks. Use this setting to disable Battery Mode for the regularly performed test. BU100RS...
Page 41
Mode A regardless of this setting. 1) When BS signal is used to stop the UPS after a power failure occurs. AC input BS signal Power output (Setting switch 4 OFF: Mode A) Power output (Setting switch 4 ON: Mode B) BU100RS...
Page 43
・ Output voltage: Inverter output in Commercial Power Mode. It is not affected by input voltage. ・ Output frequency: Always output with 60 Hz. It is not affected by input frequency. ・ Bypass output: An output stops without bypass output in the event of failure or overload. BU100RS...
0.5second 2 second 1-second 4-second intervals: intervals: 4second 1 second ● Continuous Continuous ■ Stopping the beep sound When the beep is sounding, you can stop it by pressing and holding the “STOP/TEST” switch for 0.5 to 4 seconds. BU100RS...
We recommend charging the UPS before using it. When you connect it to a commercial power source, battery charging automatically starts regardless of the ON/OFF state of the “Power” Switch and charging completes within 8 hours. BU100RS...
Page 46
UPS stop, this may be attributed to an insufficient battery charge. After connecting the AC input to the commercial power and charging the battery for at least 8 hours, go back to step 5. ・ If the problem persists after checking the 2 points above, contact us. BU100RS...
Page 47
Reconnect the AC input to the commercial power source. Status indicator returns to its normal state and the beeping sound stops. (The status is as shown below.) Status indicator Description “Power” switch “ON” Operating normally Checking the operation is now complete. BU100RS...
Power Battery Startup Bypass Self-diagnostic Inverter preparation operation test operation a few a few about 1 sec. seconds seconds 15 sec. <Note> D-1: Display the latest UPS fault mode (If there is no record for UPS fault, UPS display the BU100RS...
Page 49
● When charge of the battery does not remain If a power failure or abnormal power input is resolved after the battery is discharged completely and power output is stopped, the UPS restarts automatically and resumes power output. The expended battery begins to charge. BU100RS...
There is AC input. connector (See page “Power” switch is OFF, or OFF⇒ON. None If the condition does not Battery Disconnect or change, please replace the battery voltage is the battery pack. (See lower than 18V. page 64 to 68) BU100RS...
AC input frequency is None (ON) Use within the AC input too high. voltage/frequency range described in the AC input voltage is too specifications. None (ON) low and AC input frequency is too high. AC input voltage is too None (ON) high. BU100RS...
AC input frequency is specifications. None (ON) too low. AC input voltage and None (ON) AC input frequency are both too low. 3-4-4 Displays and beeps when there is an equipment failure (1) When "Power" switch is "ON" BU100RS...
Page 53
Switched to bypass unit. Contact the shop of operation due to purchase or our Continuous (Note 2) abnormal drop in output Electronic Systems & bypass voltage. (Note 1). Equipments Customer Support Center. BU100RS...
Page 54
(AC input OFF) occurs in bypass operation. Note 2: The displays and operations vary according to the status. Note 3: Devices such as dryers, some solenoid valves, etc., which have a half-wave rectifier. Note 4: Fan replacement does not comply with UL standard. BU100RS...
There is a problem with Failure occurred. When the unit. Contact the the “Buzzer shop of purchase or the Pause/Test” switch is OMRON Electronic Continuous pressed, the details of Systems & Equipments the error are displayed. Customer Support Center.
This timing is 10 sec. Power output stop decay 5. BU signal delay setting It is possible to set the delay time of BU signal after AC fail occur. (Setting range: 0 to 90 seconds, Default setting: 0 second) BU100RS...
Page 57
Battery Low signal (BL) Trouble signal (TR) Output signal Backup signal (BU) Deteriorated battery signal (WB) Backup power supply stop signal (BS) Input signal Remote ON/OFF signal Beep While the signal is being input, these status indications blink and the beep sounds. BU100RS...
Maximum backup time Reboot battery voltage BS signal delay BU signal delay Dry contact logic Dry contact test (2) The unit enters the “individual item setting mode” when the “Buzzer Pause/Test” switch is pressed and held (for more than 1 second). BU100RS...
Page 59
("BUT" setting) Display current setting Backup 0.1 min. Backup 0.2 min. (0.1 min. step) Backup 0.9 min. Backup 1 min. Backup 2 min. (1 min. step) Backup 10 min. Backup 20 min. (10 min. step) Backup 90 min. (next page) BU100RS...
Page 60
Charge 20% (10% step) Charge 90% Delay 0 min. BS signal delay (Default) Display ("DBS" setting) current setting Delay 0.2 min. Delay 0.5 min. Delay 1 min. Delay 2 min. (1 min. step) Delay 10 min. Disable (next page) BU100RS...
Page 61
BL signal Set and display reversed Current state of setting TR signal Current state of WB signal BL signal test Dry contact test Display TR signal test BU signal test WB signal test BS signal test Remote ON/OFF test BU100RS...
・Performed with one time per four weeks on the condition that the “Power” switch is ON When charge of the battery is not completed, the self-diagnosis test is not performed immediately. It is performed automatically after the completion of charge. BU100RS...
・ Graph of backup time (graph of initial values for products that have not been used at 25°C). The backup time becomes shorter than the graph (table) below when temperature is lower. ・ The smaller the capacity of connected devices becomes, the longer the backup time becomes. BU100RS...
Page 64
520 560 720 760 Capacity (W) Backup time table Time unit: (Minutes) Connection capacity (W) Backup time (Minutes) Note: These backup times are for reference only. Times may vary according to battery life and external environmental conditions (temperature, etc.). BU100RS...
● Do not replace the battery while the UPS is operating in backup mode. Output will stop. Additional Information When the battery replacement LED lights up/blinks and beeper sounds, press the “Buzzer Pause/Test” switch for 0.5 to 4 seconds to stop the beeper. (Lighting/blinking of “battery replacement” LED does not disappear.) BU100RS...
30°C For the first 3 years after starting When 3 years or more have passed after starting use 25°C For the first 4 years after starting When 4 years or more have passed after starting use BU100RS...
3) to loosen (turn counterclockwise) the 2 screws at the top of the front panel of the unit. (1 Pull the right side of the front panel towards you to remove it. (2 Pull the right side towards you to remove Loosen the 2 screws with hex screwdriver or wrench BU100RS...
Page 68
Turn the screw that fix the plate cover counterclockwise to remove them. (1 Pull the plate cover right (2 and pull the left side towards you to remove it. (3 Loosen the screw BU100RS...
Page 69
Hold the battery securely with both hands so as not to drop it. Red tape Pullout label (Pull this to remove) Insert a new battery into the UPS as far as it will go. BU100RS...
Page 70
Note: You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s operation is stopped, but this sound is not abnormal. Enlarged view of the connector Connect by Insert the connector’s holding here groove into the holder BU100RS...
Page 71
If you do not reset the battery life counter, a battery deterioration alarm may occur faster than the expected battery life. ・ Stick the related Battery replacement date label on the Unit after writing the battery replacement date. BU100RS...
● Doing so may cause electric shock or short-circuit. Do not put your fingers into the fan. ● While the "AC input" plug is connected to a commercial power supply, the fan rotates. ● Doing so may result in injury. BU100RS...
Pull the fan toward you to remove it. (2 Fan guard Fan recess Loosen the 4 screws Pull the fan to remove While pressing left on the tip of the fan connector (1, pull it toward you to disconnect it. BU100RS...
Page 74
Tighten the 4 screws Insert the fan to attach Attach the fan cover. (1 Use a screwdriver to securely tighten (turn clockwise) the 2 removed screws. (2 Fan replacement is now complete. Tighten the 2 screws Attach the fan cover BU100RS...
Check there are no loose screws. (See the illustration on page 24 and 26) In case of loose <Horizontal mount> Perform the work with the confirmation from page 24 section 3. <Vertical mount> Perform the work with the confirmation from page 26 section 3. BU100RS...
10. Data log save ● 11. Coordinated shutdown ● 12. Output receptacle control ● 13. Redundant power supply support ● 14. Remote UPS management ● 15. Mail send ● 16. SNMP management ● 17. Telnet connection ● 18. SYSLOG support ● BU100RS...
Page 77
16. SNMP management UPS management information can be sent to the SNMP manager. 17. Telnet connection Settings such as shutdown parameters can be made via the Telnet connection. 18. SYSLOG support UPS management information can be recorded in SYSLOG. BU100RS...
For the backup time, refer to “4-1-3 Estimated backup time”. For more information, refer to the manual in the CD-ROM. Note: When using the "PowerAct Pro", the "model name" will be displayed as "BA100R",because the program of BU100RS is in common with BA100R (another UPS model of OMRON BU100RS...
Install the “PowerAct Pro” or “Simple Shutdown Software” to the PC you want to shut down. Note: Installation method: For “PowerAct Pro”, refer to the installation guide (for Windows) on the CD-ROM. Refer to the manual for “Simple Shutdown Software”. BU100RS...
Page 80
● If a power failure occurs and then the power is restored while auto shutdown is still in progress, UPS output will stop temporarily after the set time elapses. After shutdown is finished, do not turn on the computer until the UPS has finished restarting. BU100RS...
You can stop the output of the UPS by inputting the voltage signal (HIGH) that lasts at least 10 seconds from the outside. Note 2: Connection terminals are at contact signal port pins 6, 7 and the remote ON/OFF port (See also "3-1-4 Setting Switch"). BU100RS...
Voltage between terminals: 5 VDC Current when closed: 10 mA max. 6-1-6 Contact Signal circuit ● Signal output (BL, TR, BU, WB) ● Remote ON/OFF ● UPS Stop Signal input (BS) 470Ω Remote ON/OFF (+) 2.4V 560Ω Remote ON/OFF (-) BU100RS...
If you do not want to start the connected devices, turn OFF their switches or set the auto startup setting after recovery from power failure (“Setting” switch 2) to ON (Auto startup is not performed). BU100RS...
Turn OFF all power to the unit and connected devices, and reduce the number of connected continuously devices. Then, turn the power to the unit and connected devices back ON and check whether " " is displayed on the status indicator. See also “3-4 Interpreting beeps and displays”, BU100RS...
9 References 9-1 Specifications 9 References 9-1 Specifications Model BU100RS Full-time inverter supply method (Automatic Switching) Operation method Method Forced air cooling Cooling method 100/110/115/120 VAC Rated input voltage 70±2 to 146±2 V AC (with less than 90% connection load) Input voltage range 80±2 to 146±2 V AC (with 90% or more connection load)
1.7 years 3.5 years 5 years BU100RS Basically, the ambient temperature has a high influence on the battery life. ■ The periodic recharges are required even if the battery is stored. The battery self-discharges even if the UPS is not used (i.e., leaving the battery not charged), and it deteriorates the battery.
9 References 9-4 China RoHS Information 9-4 China RoHS Information BU100RS...
Page 102
No part or whole of this manual may be reproduced without permission. The contents of this manual are subject to change without notice. Corporation K1L-D-15078E...