Omron BU5002R Instruction Manual page 70

Ups/200 to 240 v
Table of Contents

Advertisement

3 Checking and starting the operation
3-1 Names and functions of each part of the operation and display sections
■ Errors other than the battery errors
UPS
status
Over
load
Output
short
circuit
Output
voltage
high
Output
voltage
low
Battery
voltage
high
Battery
voltage
low
70
Symbol
Icon
Buzzer
Intermittent,
at intervals
(Not
(Not
of 0.5
e 1)
e 1)
seconds
● Continuous OFF
● Continuous OFF
(Not
(Not
e 1)
e 1)
● Continuous
(Not
(Not
e 1)
e 1)
● Continuous
(Not
(Not
e 1)
e 1)
● Continuous
(Not
(Not
e 1)
e 1)
● Continuous
(Not
(Not
e 1)
e 1)
Text
Output Charge
displayed
Description
on top
The load of the
connected devices
exceeds the rated
capacity. If the
operation of UPS is
ON
ON
continued, it is
or
or
Fault-E9
switched to bypass
OFF
OFF
operation in the case
of normal operation,
and output stops in
the case of backup
operation.
There is a fault
due to overload,
OFF
Fault-EO
so output has
stopped.
Output has
stopped due to a
short circuit on the
connected device
ON
Fault-ES
side or a major
connection
capacity overload.
The output voltage is
high, and thus if the
operation of UPS is
ON
continued, it is
ON
or
switched to bypass
or
Fault-E1
operation in the case
Disch
OFF
of normal operation,
arging
and output stops in
the case of backup
operation.
The output voltage is
low, so if continued in
ON
ON
normal operation, it
or
or
Fault-E2
will change to bypass
Disch
operation, and if in
OFF
arging
backup operation
output will stop.
The battery charging
voltage is high, and
thus if the operation of
ON
UPS is continued, it is
ON
or
switched to bypass
or
Fault-E3
operation in the case
Disch
OFF
of normal operation,
arging
and output stops in
the case of backup
operation.
The battery charging
voltage is low, so if
ON
continued in normal
ON
or
operation, it will
or
Fault-E4
change to bypass
Disch
OFF
operation, and if in
arging
backup operation
output will stop.
○: ON, ●: OFF
Solution
Turn off the power
switches of all the
devices connected to
the UPS, and after
reducing the
connected devices,
turn on the "Power"
switches of the UPS
and the connected
devices.
Note: The load
amount can be
checked from
the LCD Menu
by "1.
Measurements"-
"Load Meter"
Check whether a short
circuit is occurring on the
AC input of the
connected device, or the
connected capacity is
exceeding the rated
capacity.
Turn off the power
switches of all the
devices connected to
the UPS, and turn on
the power switch of
the UPS only. If the
displayed content
does not change, the
UPS is faulty. Contact
the shop of purchase.
Note: The output
voltage can be
checked from
the LCD Menu
by "1.
Measurements"-
"Input/Output
Meter". The
battery voltage
can be checked
by "1.
Measurements"
- "Battery
Meter".
BU5002R/BU3002R/BU3002RH

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bu3002rBu3002rh

Table of Contents