Caution (for installation and connection)
When using in 100 V output mode, check that the output voltage is set to
100 V before turning on the power switch.
⚫ When 100 V device is connected during output in 200 V mode, there is a risk of
breakdown of the device or fire.
⚫ The output voltage can be set from the LCD menu by [3. Settings] - [In/Out
Settings] - [O/P Voltage].
⚫ The upper limit of capacity changes in 100 V output mode.
BU5002R:
BU3002R/BU3002RH:
⚫ In 100 V output mode, it is not possible to switch to bypass operation.
⚫ In 100 V output mode, it is not possible to operate in Eco mode (commercial direct
output).
Do not wet this unit or splash water on it.
Stop using the product if it is dropped.
⚫ There is a risk of electric shock or fire.
⚫ If the unit gets wet or is dropped, immediately stop using it, turn the AC input off,
and have it inspected and repaired.
⚫ For repairs, contact the shop of purchase.
When service life of a battery has expired, immediately replace it, or stop
using this unit.
⚫ If such battery is used without replacing, there is a risk of fire or electric shock due
to liquid leakage.
Ambient
Anticipated
temperature
40°C
1.7 years
25°C
5 years
Wipe off the dust on the plug, the receptacle, and the terminal block
occasionally.
⚫ It may cause a fire if the dust adheres for a long time.
⚫ Stop all the connected devices and the unit and unplug the "AC input" plug from the
power outlet (commercial power supply) before wiping off the dust.
⚫ Use a dry cloth to wipe the unit without using any chemicals containing thinner,
benzine, or alcohol as there is a risk of it catching fire.
Do not use this unit in a sealed location or cover it with a cover.
⚫ There is a risk of abnormal heat generation and occurrence of a fire.
⚫ Depending on the environment of use, hydrogen gas may be generated from the
battery, which could cause a crack or an explosion. Ventilate the area around the
unit.
BU5002R/BU3002R/BU3002RH
2500VA/2250W
1500VA/1350W
* The table on the left shows the anticipated life
life
under standard conditions of usage, but they
are not guaranteed values.
Safety precautions
17