Download Print this page

Siemens SINAMICS G130 Operating Instructions Manual page 16

Dv/dt filter plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:

Advertisement

General
Table 2- 2
Max. pulse frequency when a dv/dt filter is used in units with a rated pulse frequency of 2 kHz
Article no.
Power [kW]
6SL3310-...
1GE32-1AA3
110
1GE32-6AA3
132
1GE33-1AA3
160
1GE33-8AA3
200
1GE35-0AA3
250
Table 2- 3
Max. pulse frequency when a dv/dt filter is used in units with a rated pulse frequency of 1.25 kHz
Article no.
Power [kW]
6SL3310-...
1GE36-1AA3
315
1GE37-5AA3
400
1GE38-4AA3
450
1GE41-0AA3
560
1GF31-8AA3
110
1GF32-2AA3
132
1GF32-6AA3
160
1GF33-3AA3
200
1GF34-1AA3
250
1GF34-7AA3
315
1GF35-8AA3
400
1GF37-4AA3
450
1GF38-1AA3
560
1GH28-5AA3
75
1GH31-0AA3
90
1GH31-2AA3
110
1GH31-5AA3
132
1GH31-8AA3
160
1GH32-2AA3
200
1GH32-6AA3
250
1GH33-3AA3
315
1GH34-1AA3
400
1GH34-7AA3
450
1GH35-8AA3
560
1GH37-4AA3
710
1GH38-1AA3
800
14
Output current for a
pulse frequency of 2 kHz [A]
Line voltage 3 AC 380 V ... 480 V
210
260
310
380
490
Output current for a
pulse frequency of 1.25 kHz [A]
Line voltage 3 AC 380 V ... 480 V
605
745
840
985
Line voltage 3 AC 500 V ... 600 V
175
215
260
330
410
465
575
735
810
Line voltage 3 AC 660 V ... 690 V
85
100
120
150
175
215
260
330
410
465
575
735
810
Max. pulse frequency when a dv/dt filter is used
4 kHz
4 kHz
4 kHz
4 kHz
4 kHz
Max. pulse frequency when a dv/dt filter is used
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 11/2017, A5E00692302A

Advertisement

loading