ABB Relion 650 Series Commissioning Manual page 70

Busbar protection version 1.1 iec
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 9
Troubleshooting
1
GUID-31DF5495-91F1-4A4B-8FD5-50625038961E V1 EN-US
Figure 10: Testing a trip contact
1 Trip contact under test
2 Current limiting resistor
To check the status of the output circuits driving the output relay via the LHMI, select
Main menu/Tests/Binary output values/Binary output modules and then navigate to the
board with the actual binary output to be checked.
Test and change the relay state manually.
1.
2.
3.
64
2
A
To set the IED to test mode, select Main menu/Tests/IED testmode1:TESTMODE/
TestMode and set the parameter to
To operate or force the output relay to operate, select and then navigate to the
board with the actual binary output relay to be operated/forced.
Select the BOn_PO to be operated/forced and use
actual output relay.
In PCM600, only the result of these operations can be checked by right-clicking the
product and selecting Signal Monitoring tool and then navigating to the actual I/O-
board and the binary input in question. The activated output signal is indicated with
a yellow-lit diode. Each BOn_PO is represented by two signals. The first signal in
LHMI is the actual value 1 or 0 of the output, and in PCM600 a lit or dimmed diode.
The second signal is the status Normal or Forced. Forced status is only achieved
when the BO is set to
Forced or operated on the LHMI.
© Copyright 2011 ABB. All rights reserved
V
On .
and
1MRK 505 264-UEN A
or
to operate the
Busbar protection REB650
Commissioning manual