Starting Up; Factory And Site Acceptance Testing; Commissioning Checklist - ABB Relion 650 Series Commissioning Manual

Busbar protection version 1.1 iec
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 264-UEN A
Section 4
4.1

Factory and site acceptance testing

Testing the proper IED operation is carried out at different occasions, for example:
Acceptance testing
Commissioning testing
Maintenance testing
This manual describes the workflow and the steps to carry out the commissioning testing.
Factory acceptance testing (FAT) is typically done to verify that the IED and configuration
meets the requirements by the utility or industry. This test is the most complex and in depth,
as it is done to familiarize the user to a new protection or to verify a new configuration. The
complexity of this testing depends on several factors.
New IED type
New configuration
Pre-configured
Modified existing configuration
Site acceptance testing (SAT or commissioning testing) is typically done to verify that the new
installed IED is correctly set and connected to the power system. SAT requires that the
acceptance testing has been performed and that the application configuration is verified.
Maintenance testing is a periodical verification that the IED is healthy and has correct settings
depending on changes in the power system. There are also other types of maintenance
testing.
4.2

Commissioning checklist

Before starting up commissioning at site, check that the following items are available.
Single line diagram
Protection block diagram
Circuit diagram
Setting list and configuration
RJ-45 Ethernet cable (CAT 5)
Three-phase test kit or other test equipment depending on the complexity of the
configuration and functions to be tested.
PC with PCM600 installed along with the connectivity packages corresponding to the IED
used
Administration rights on the PC to set up IP addresses
Product documentation (engineering manual, installation manual, commissioning manual,
operation manual, technical manual and communication protocol manual)
Busbar protection REB650
Commissioning manual

Starting up

© Copyright 2011 ABB. All rights reserved
Section 4
Starting up
GUID-38C2B5FA-9210-4D85-BA21-39CE98A1A84A v1
GUID-93D14E4E-5DDE-4D37-84A6-2DF0656AB73D v2
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reb650

Table of Contents