ABB Relion 650 Series Commissioning Manual page 29

Busbar protection version 1.1 iec
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 264-UEN A
IEC09000356 V1 EN-US
Figure 4:
3.
Select the TCP/IP protocol from the list of configured components using this connection
and click Properties.
IEC09000357 V1 EN-US
Figure 5:
4.
Select Obtain an IP address automatically if the parameter
IED.
IEC09000358 V1 EN-US
Figure 6:
5.
Select Use the following IP address and define
port is used and if the
Figure
Busbar protection REB650
Commissioning manual
IEC09000356-1-en.vsd
Right-click Local Area Connection and select Properties
IEC09000357-1-en.vsd
Select the TCP/IP protocol and open Properties
IEC09000358-1-en.vsd
Select: Obtain an IP address automatically
IP address is not set to be obtained automatically by the IED, see
7. The IP address must be different from the IP address chosen for the IED.
© Copyright 2011 ABB. All rights reserved
DHCPServer is set to On in the
IP address and Subnet mask if the front
Section 4
Starting up
23