◆ 312 Input voltage
Sets the input voltage (3φ3W, 1φ2W) or phase voltage full-scale (1φ3W).
In 3φ3W/1φ2W and 1φ3W, the contents of a setting are different.
Selection by + and - , set value is updated by SET .
Default setting:300V (1φ3W)
Default setting:110V (3φ3W,1φ2W or no designation)
・3φ3W,1φ2W
110V
Setting of 300V, Output of phase voltage is AC0~150V/DC4~12mA.
Setting of 150V, Output of phase voltage is AC0~150V/DC4~20mA.
New setting
Setting No.
Input-voltage rating (3φ3W)
(2) 321~326 Analog output adjustment 【With option】
The bias and span of each analog output are adjusted.
321
Ao1 BIAS
adjustment
MAX/MIN
RESET/SHIFT
326
Ao3 SPAN
adjustment
◆ 321 AO(Analog output) 1 bias adjustment,
323 AO(Analog output) 2 bias adjustment,
325 AO(Analog output) 3 bias adjustment.
The bias of each analog output is adjusted.
Setting range:±10.0% (0.1% step)
Selection by + and - , set value is updated by SET .
◆ 322 AO(Analog output) 1 span adjustment,
324 AO(Analog output) 2 span adjustment,
326 AO(Analog output) 3 span adjustment.
The span of each analog output is adjusted.
Setting range:±10.0% (0.1% step)
Selection by + and - , set value is updated by SET .
・1φ3W
150V
220V
Now setting
Setting No.
Phase-voltage full scale (1φ3W)
322
MAX/MIN
Ao1 SPAN
RESET/
adjustment
SHIFT
RESET/
325
SHIFT
Ao3 BIAS
MAX/MIN
adjustment
300V
New setting
323
MAX/MIN
Ao2 BIAS
RESET/
adjustment
SHIFT
RESET/SHIFT
RESET/
324
SHIFT
Ao2 SPAN
MAX/MIN
adjustment
37
UN
WN alternate display
(Phase display U-W-N)
Now setting
MAX/MIN
Ao1 span adjustment
SVLC-212-175