Appendix D Reference; Appendix D.1. Led Functions; Figure 27: Fs-Qs-10Xx Leds - SMC Networks FieldServer QuickServer FS-QS-12 0 Series Startup Manual

Table of Contents

Advertisement

Appendix D Reference

Appendix D.1. LED Functions

Light
Description
SPL LED will be on when a configured node in the QuickServer is detected as being offline. See
SPL
Node overview screen of the FS-GUI for further details.
For LonWorks units, LED will light until the unit is commissioned on the LonWorks network.
RUN LED will flash 20 seconds after power up, signifying normal operation. The QuickServer will be
RUN
able to access FS-GUI (refer to Section
During the first 20 seconds, the LED should be off.
The ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red
light will indicate there is a system error on the FieldServer. If this occurs, immediately report the
ERR
related "system error" shown in the error screen of the FS-GUI interface to FieldServer Technologies
for evaluation.
On normal operation of FS-QS-10XX, the RX LED will flash when a message is received on the field
RX
port of the QuickServer.
On normal operation of FS-QS-10XX, the TX LED will flash when a message is sent on the field port
TX
of the QuickServer.
PWR
This is the power light and should show steady green at all times when the QuickServer is powered.

Figure 27: FS-QS-10XX LEDs