6
OPERATION
6.1
Power up the device
Apply power to the device. Ensure that the power supply used complies with the specifications provided
in. Ensure that the cable is grounded using the "Frame GND" terminal. The QuickServer is factory set for
9-30VDC or 12-24VAC.
6.2
Connect the PC to the QuickServer over the Ethernet port
Connect an Ethernet cable between the PC and QuickServer or connect the QuickServer and the
PC to the Hub/switch using a straight CAT5 cable.
The Default IP Address of the QuickServer is 192.168.2.101, Subnet Mask is 255.255.255.0.
Virus protection and firewall software should temporarily be disabled if connection problems are
experienced.
PWR+
PWR-
Figure 14: Connecting Power
Figure 15: Ethernet Port
Page 19 of 46
QuickServer Start-Up Guide
FG
Ethernet Port