10 Servicing

The work described in this section is only to
be performed by personnel qualified for the
assignment accordingly.
We recommend inspection and testing ac-
cording to Table 10-1 which can be per-
formed while the process is running:
The pneumatic connections have filters with
plastic rims (order no. 0550-0213) which
can be removed for cleaning or replacement.
Table 10-1: Recommended inspection and testing
Inspection and testing
Check the markings, labels and nameplates on
the converter for their readability and
completeness.
Check air connections for leakage.
Check air lines for leakage.
Check the current or voltage line.
Check the quality of the conversion from the input
to output.
Check the air filter and trap installed in the
upstream air reducing station.
EB 6126 EN

10.1 Periodic testing

Periodic testing can help prevent possible
malfunctions before they occur. Operators
are responsible for drawing up an inspection
and test plan.
Action to be taken in the event of a negative
result
Immediately renew damaged, missing or incorrect
nameplates or labels.
Clean any inscriptions that are covered with dirt
and are illegible.
Tighten air connections. Renew them if need be.
Renew air lines.
If lines are loose, open the plug connector case
and tighten the screws at the terminal (see the
'Connections' section).
Renew damaged lines.
Tune zero and span (see the 'Start-up' section).
Clean the air filter and trap according to the
instructions given by the manufacturer of the air
reducing station. Renew them if need be.