9. Analyze the combustion. Follow the combustion analyzer manufacturer's
instructions and the general guidelines below.
Use the access hole in the exhaust stack.
Take several samples as the heater warms.
Take the final sample just before the heater reaches 71°C (160°F).
10.Re-adjust the air setting(s) if necessary until the smoke spot test and
combustion analysis are within the following parameters:
O
2
Smoke spot: 1 or less
Result
You have now set up the burner.
wc_tx001669gb.fm
content: 4–6%
79
Burner Setup