Securing the Chassis
This chapter describes how to secure the Cisco NCS 4016 chassis in the rack.
To install two Cisco NCS 4016 chassis in a single rack, you will need to have a minimum vertical opening
Note
of 48 RU. If you are using the DC Power Front Connection Adapter, only one chassis will fit into the rack.
•
•
•
•
•
Preparing the Rack for Chassis Installation
Install the Cisco NCS 4016 chassis into one of the following standard racks:
• ANSI 19-inch or 23-inch (2- or 4-post)
• ETSI
For the ANSI 19-inch rack, the minimum front opening must be 17.72 inches (450 mm) to allow for
Note
chassis insertion.
If you are installing a single chassis in a rack, the chassis must go in the middle or bottom portion of the rack
or follow your company chassis mounting practices.
At the bottom of the rack, keep 1 rack unit free to allow for removal of the bottom fan tray.