SM Split CS Series Heat Pump
UPM LED Status Indicator (Blink Code)
Information
The LED status indicator is found on the UPM
board. See Fig. 6 on page #16.
Indication
Color
Blinks
GREEN
Solid
RED
1
RED
2
RED
3
RED
4
RED
5
RED
6
Table 15
UPM LED Status Indications
Compressor Ohms
Model
Start Winding
SM024
1.64
SM036
1.52
SM048
1.86
SM060
1.63
Tolerance +/- 7%. All resistance values must be
measured with compressor at room temperature.
Table 16
Compressor Ohms
SM Split CS Series Heat Pump
Description
18–30 VAC power is present
High-pressure lockout
Low-pressure lockout
Freeze sensor lockout
Condensate overflow
Brownout
Evaporator Freeze condition
Run Winding
1.30
0.88
0.52
0.39
Subject to change without prior notice