LM Split CS Series Heat Pump CONTENTS Compressor Ohms .............31 Operating Temperatures and Pressures......32 Document Conventions ............3 Key to Symbols............3 Maintenance ..............36 Water Side Pressure Drop in PSIG ........36 Safety Warnings..............3 Decommissioning Information ........... 37 Model Nomenclature ............4 Protecting the Environment .........37...
LM Split CS Series Heat Pump Document Conventions | 3 DOCUMENT CONVENTIONS Key to Symbols WARNING: When working on equipment, always observe precautions described in Warnings the literature, tags, and labels attached to Warnings in this document are identified by the unit.
4 | Model Nomenclature LM Split CS Series Heat Pump MODEL NOMENCLATURE Fig. 1 Model Nomenclature Subject to change without prior notice 8733827906 (2021/11) LM Split CS Series Heat Pump...
6 | LM Split CS Standard Package LM Split CS Series Heat Pump LM SPLIT CS STANDARD PACKAGE A heat pump operating under extreme conditions will have limitations on air/fluid flow rates and/or temperatures. NOTICE: 50° F Minimum Entering Water...
LM Split CS Series Heat Pump Unit Installation | 7 UNIT INSTALLATION Air Handler Location This section contains information on the following: Locate the air handler unit in an indoor area that allows easy removal of the filter and access panels,...
8 | Installation LM Split CS Series Heat Pump Use flexible hoses between the unit and the rigid system to avoid possible vibration. Vibration Pad NOTICE: Never use flexible hoses of a recommended smaller inside diameter than that of the fluid connections on the unit.
LM Split CS Series Heat Pump Refrigerant Lines | 9 • Oil is continually being circulated with the refrigerant so, oil return to the compressor is prevent leaks possible heat always a consideration in line sizing. Suction exchanger fouling, use Teflon tape sealer...
Page 10
10 | Refrigerant Lines LM Split CS Series Heat Pump Valve Sizing Chart NOTICE: A filter drier is already installed Unit Size Line Valve from factory in the LM Split Condensing Type Conn. (Allen) section unit. No additional/external filter Size Wrench drier required.
LM Split CS Series Heat Pump Water Quality Table | 15 Electrical Refer to electrical component box layout. (See Fig. 5) DANGER: UNIT OPERATION AND SAFETY HAZARD Field wiring must comply with local and national electric codes. WARNING: UNIT OPERATION AND SAFETY...
16 | Safety Devices and the UPM Controller LM Split CS Series Heat Pump Safety Devices and the UPM Controller If the thermostat is provided with a malfunction light powered off of the common (C) side of the transformer, a jumper between “R”...
Page 17
LM Split CS Series Heat Pump Safety Devices and the UPM Controller | 17 For Reference UPM Board Factory Default Settings Only TEMP 26°F LOCKOUT RESET ALARM PULSE TEST Table 10 UPM Board Factory Default Settings Fig. 7 Sensor location...
Page 18
18 | Safety Devices and the UPM Controller LM Split CS Series Heat Pump to R, the board must be manually powered off drops below or remains at the freeze-limit trip for 30 seconds, the controller will shut the and powered back on to exit the hard lock out.
LM Split CS Series Heat Pump Typical System Setup | 19 TYPICAL SYSTEM SETUP For Reference Only. A typical setup is shown for illustration purposes only. Fig. 9 Typical system setup [1] Flex Duct Connection [2] Low Voltage Control Connection...
20 | Typical System Setup LM Split CS Series Heat Pump SPECIFIC APPLICATION CONSIDERATIONS Teflon tape sealer must be used when connecting to the unit to insure against Well Water Systems leaks and possible heat exchanger fouling. Copper is adequate only for ground water that is not high in mineral content.
LM Split CS Series Heat Pump Post-Installation System Checkout | 21 POST-INSTALLATION SYSTEM SYSTEM OPERATION CHECKOUT UNIT START-UP After completing the installation and before 1. Place the UPM board in “Test” mode. energizing the unit, the following system checks 2. Set the thermostat to the highest setting.
Page 22
22 | Sequence of Operation LM Split CS Series Heat Pump Some accessories have a built-in delay, and hence, compressor operation is not immediate. See “Field-Installed Accessories” section on page #23 for more detail. When the thermostat calls for second-stage cooling (Y2) the second stage (or full-compressor capacity) is initiated.
LM Split CS Series Heat Pump Field-Installed Accessories | 23 FIELD-INSTALLED ACCESSORIES SmartStart Assist A number of field-installed accessories are The LM series is available with the SmartStart available on LM Series of Heat Pumps. The Assist device as a field-installed accessory. This...
24 | Field-Installed Accessories LM Split CS Series Heat Pump SmartStart Assist Specifications SmartStart Assist Specifications Rated Operational Voltage: 208/230VACrms +/- 15% 50-60 Hz Environmental Operating Range: -4° to 149°F (-20° to 65°C); < 95% @ 40 C relative humidity,...
Page 25
LM Split CS Series Heat Pump Field-Installed Accessories | 25 Fig. 13 SmartStart Assist Modes of Operations (Overcurrent Condition and Incomplete Ramp Alarm) SmartStart Assist Modes of Operation Notes 4. In the case of an under voltage, the SmartStart Assist will shut down and the red LED flashes 1.
Page 26
26 | Field-Installed Accessories LM Split CS Series Heat Pump 6. A detection circuitry provides protection in case of a faulty starting capacitor EMR. In such situations, the red LED will flash four times for five minutes. SmartStart Assist will check the...
LM Split CS Series Heat Pump Check-Out Sheet | 27 CHECK-OUT SHEET Customer Data Customer Name Date Address Phone Unit Number Unit Nameplate Data Unit Make Model Number Serial Number Refrigerant Charge (oz) Compressor: RLA Blower Motor: FLA (or NPA)
28 | Troubleshooting LM Split CS Series Heat Pump TROUBLESHOOTING A possible fault may be one or a combination of causes and solutions. Check each cause and adopt “process of elimination” and or verification of each before making any conclusion.
Page 29
LM Split CS Series Heat Pump Troubleshooting | 29 Unit Troubleshooting Problem Possible Cause Checks and Corrections Unit Oversized Recalculate heating and or cooling loads. If the thermostat is installed near a supply air grill, UNIT SHORT Thermostat relocate thermostat. Adjust the heat anticipator.
30 | Troubleshooting LM Split CS Series Heat Pump SmartStart Assist Troubleshooting Red Led Relay Condition Action Contact* FULLY ON + 11/12 Min. recovery time between starts Auto reset when minimum recovery and/or recovery time between stop to time elapses...
LM Split CS Series Heat Pump Troubleshooting | 31 UPM LED Status Indicator (Blink Code) Information The LED status indicator is found on the UPM board. See Fig. 6 on page #16. Indication Color Blinks Description GREEN Solid 18–30 VAC power is present...
32 | Operating Temperatures and Pressures LM Split CS Series Heat Pump OPERATING TEMPERATURES AND PRESSURES Operating Temperatures and Pressures Cooling Heating Water Entering Suction Discharge Water Suction Discharge Temp. Water Water Pressure Pressure Temp. Temp. Pressure Pressure Drop Temp.
Page 33
LM Split CS Series Heat Pump Operating Temperatures and Pressures | 33 Operating Temperatures and Pressures Cooling Heating Water Entering Suction Discharge Water Suction Discharge Temp. Water Water Pressure Pressure Temp. Temp. Pressure Pressure Drop Temp. Model Temp. F Flow...
Page 34
34 | Operating Temperatures and Pressures LM Split CS Series Heat Pump Operating Temperatures and Pressures Cooling Heating Water Entering Suction Discharge Water Suction Discharge Temp. Water Water Pressure Pressure Temp. Temp. Pressure Pressure Drop Temp. Model Temp. F Flow...
Page 35
LM Split CS Series Heat Pump Operating Temperatures and Pressures | 35 Operating Temperatures and Pressures Cooling Heating Water Entering Suction Discharge Water Suction Discharge Temp. Water Water Pressure Pressure Temp. Temp. Pressure Pressure Drop Temp. Model Temp. F Flow...
36 | Maintenance LM Split CS Series Heat Pump MAINTENANCE Water Side Pressure Drop in PSIG Series Water PD @ 77°EWT DANGER: ELECTRICAL HAZARD with Water Before performing service or maintenance operations on the system, turn off the main power to the unit. Electrical shock will cause personal injury or death.
LM Split CS Series Heat Pump Decommissioning Information | 37 Components DECOMMISSIONING INFORMATION Only trained and qualified technicians are allowed Many parts in the Heat Pump can be fully to decommission and dispose of equipment recycled at the end of the product life.
38 | Wiring Diagrams LM Split CS Series Heat Pump WIRING DIAGRAMS Fig. 15 Wiring Diagrams FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. Subject to change without prior notice...
40 | Dimensional Drawings LM Split CS Series Heat Pump DIMENSIONAL DRAWINGS Fig. 18 Dimensional Drawings FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. Subject to change without prior notice...
LM Split CS Series Heat Pump Terminology | 41 TERMINOLOGY servicing or prior to the disposal of the products or equipment. Acronyms AHJ — Authority Having Jurisdiction Recycling — Referring to the reuse of a recovered fluorinated-greenhouse gas following a basic cleaning ECM —...