Safety Information
Hazards
DANGER! - Ignoring the following may result in injury
1. This equipment can endanger life by
exposure to rotating machinery and
high voltages.
2. The equipment must be permanently
earthed due to the high earth leakage
current, and the drive motor must be
connected to an appropriate safety
earth.
3. Ensure all incoming supplies are
isolated before working on the
equipment. Be aware that there may be
more than one supply connection to the
drive.
4. There may still be dangerous voltages
present at power terminals (motor
output, supply input phases, DC bus and
the brake, where fitted) when the motor
is at standstill or is stopped.
Product Warnings
Caution
Risk of
electric
shock
Caution
Refer to
document
ation
5. For measurements use only a meter
to IEC 61010 (CAT III or higher).
Always begin using the highest
range.
CAT I and CAT II meters must not
be used on this product.
6. Allow at least 5 minutes for the
drive's capacitors to discharge to safe
voltage levels (<50V). Use the
specified meter capable of measuring
up to 1000V dc & ac rms to confirm
that less than 50V is present between
all power terminals and earth.
7. Unless otherwise stated, this product
must NOT be dismantled. In the
event of a fault the drive must be
returned. Refer to "Routine
Maintenance and Repair".
!
Earth/Ground
Protective
Conductor
Terminal