Shutdown Alarms - Woodward easYgen-1600 Operation Manual

Genset control
Hide thumbs Also See for easYgen-1600:
Table of Contents

Advertisement

No.
Items
10
Oil Pressure Sensor Open
11
Maintenance Warn
12
High Temp.
13
Low Oil Pressure
14
Input Warn
15
Failed To Charge
16
Over Power
17
ECU Warn
4.1.3

Shutdown Alarms

When controller detects shutdown alarm, it will send signal to open breaker and shuts
down generator.
No.
Items
1
Emergency Stop
2
High Temp. Shutdown
3
Low Oil Pressure Shutdown
4
Over Speed Shutdown
5
Under Speed Shutdown
6
Loss Of Speed Signal
Shutdown
7
Genset Over Voltage
Shutdown
8
Genset Under Voltage
Shutdown
9
Genset Over Current
Shutdown
10
Failed To Start
11
Over Freq. Shutdown
37785A
Description
When sensor hasn't connected to corresponding port, controller will send
warning alarm signal and it will be displayed in LCD.
When genset running time is longer than maintenance time of user setting, and
the maintenance action is set as warning, controller send warning alarm signal
and it will be displayed in LCD. When maintenance action type is set as "Not
used", maintenance alarm reset.
When the water/cylinder temperature of genset is higher than threshold and
Enabled High Temp. Stop Inhibited or Input High Temp. Stop Inhibited is active,
controller will send warning alarm signal and it will be displayed in LCD.
When the oil pressure of genset is less than threshold and Enabled Low Oil
Pressure Stop Inhibited or Input Low Oil Pressure Stop Inhibited is active,
controller will send warning alarm signal and it will be displayed in LCD.
When external input is active, controller will send warning alarm signal and it
will be displayed in LCD.
When Failed To Charge input is active, controller will send warning alarm signal
and it will be displayed in LCD.
If over power detection is enabled, when the controller detects that the over
power value (power is positive) has exceeded the pre-set value and the action
select "Warn", it will initiate a warning alarm.
If an error message is received from ECU via J1939, it will initiate a warning
alarm.
Description
When controller detects emergency stop signal, it will send a stop alarm signal
and it will be displayed in LCD.
When the temperature of water/cylinder is higher than set threshold, controller
will send a stop alarm signal and it will be displayed in LCD.
When oil pressure is lower than threshold, controller will send a stop alarm
signal and it will be displayed in LCD.
When genset speed is higher than set threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
When genset speed is lower than set threshold, controller will send a stop alarm
signal and it will be displayed in LCD.
When rotate speed is 0 and delay is not 0, controller will send a stop alarm
signal and it will be displayed in LCD.
When genset voltage is higher than threshold, controller will send a stop alarm
signal and it will be displayed in LCD.
When genset voltage is under set threshold, controller will send a stop alarm
signal and it will be displayed in LCD.
When genset current is higher than set threshold and delay is not 0, it will send
a stop alarm signal and it will be displayed in LCD.
Within set start times, if failed to start, controller will send a stop alarm signal
and it will be displayed in LCD.
When genset frequency is higher than set threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
easYgen-1600
4 Appendix
4.1 Alarms and Warnings
27