4 Mounting
4.1 Vibration dampers
The compressor can be rigidly mounted if there is no
risk of damage caused by vibration in the pipeline sys-
tem connected to it. Otherwise the compressor must be
mounted on vibration dampers.
Compressor
Tab. 2: Vibration dampers 2MME-07K .. 6PME-40K, 2NSL-05K .. 4CSL-12K
Compressor
4VSL-15K .. 4NSL-30K
Tab. 3: Vibration dampers 4VSL-15K .. 4NSL-30K
KB-120-8
Mounting the suction gas and discharge gas lines:
• Place the compressor on the vibration dampers or
mount it rigidly. In this position (= operational posi-
tion), connect the suction gas and discharge gas
lines and make sure that they are stress-free. Select
the vibration dampers according to the following
tables:
Kit number, article number
(4 pieces)
370 005 02
370 005 02
370 005 03
370 005 03
370 000 19
370 000 20
370 000 20
Kit number, art-
Hardness
icle number
(2 pieces)
Crankcase side
370 002 11
60 Shore
Hardness
60 Shore
60 Shore
55 Shore
55 Shore
43 Shore
55 Shore
55 Shore
Kit number, art-
Hardness
icle number
(2 pieces)
Motor side
370 002 10
65 Shore