Expert Functions
5.2 Extending a PROFIdrive message frame
5.2.3
Extending the PROFIdrive message frame in S7T Config
In S7 Technology V4.1 and higher, there is an option to extend message frames directly
in the SINAMICS message frame configuration in S7T Config.
Procedure
1. In S7T Config, open the message frame configuration of SINAMICS S120.
2. Select the drive object.
3. Click "Adapt message frame configuration" and then select "Add message frame
4. Click "Interconnections/Diagnostics" to open the message frame configuration of the drive
5. Clear the "Suppress inactive interconnections" option to display the added words of the
6. Change the desired message frame properties and close the message frame
7. Click "Align message frame with HW Config: Set up addresses" to perform alignment with
8. Choose "Save and compile" to activate the changes in the S7T Config project.
138
extension".
object. The individual control and status words of the utilized message frame are
displayed there.
message frame extension. These are designated as "user-defined".
configuration.
HW Config.
Connection of the SINAMICS S120 to the Technology CPU
Product Information, 09/2011, A5E00480378-04