6 Operation
ImPS
ImPR
OU1
OU2
ASP
32
Output 1 as pulse output
ImPS
is only active when
Configuring quantity monitoring through pulse output
Select
ImPR
and set to YES.
Pulse repetition is active. Output 1 emits a counting pulse
each time the value set in
Configure the quantity monitoring using the preset coun-
ter.
Select
ImPR
and set to NO.
Pulse repetition is not active. The output switches ON
when the value set in
switched until the counter is reset.
For further details Setting the preset counter / pulse
value (ImPS), page 36.
Configuration for output 1
5 functions can be set:
Hno
= Hysteresis function / normally open (NO)
Hnc
= Hysteresis function / normally closed (NC)
Fno
= Window function / normally open (NO)
Fnc
= Window function / normally closed (NC)
Output signal for consumption quantity:
ImP
= Pulse output
Configuration for output 2
6 functions can be set:
Output signals for flow measurement:
Hno
= Hysteresis function / normally open (NO)
Hnc
= Hysteresis function / normally closed (NC)
Fno
= Window function / normally open (NO)
Fnc
= Window function / normally closed (NC)
I
= Analogue signal (4 to 20 mA)
Alternatively: Configure output 2 (pin 2) as an input for an
external reset signal.
Setting:
OU2
=
InD
Analogue starting point
Measurement value at which 4 mA is output.
active when
OU2
OU1
= ImP.
ImPS
is reached.
ImPS
is reached. It remains
= I.
ASP
is only