Class I, IPE, with BENNING MA 2-16
IPE
:
only after passed RInsu measurement
dir.
´
Connection diagram
VDE 0701-0702, VDE 0751-1, VDE 0544-4
Circuit diagram
VDE 0701-0702, VDE 0751-1, VDE 0544-4
(switch position IPE direct)
Connect the BENNING MA 2-16 measuring adapter to the
BENNING ST 755/ ST 760 appliance tester according to the
connection conditions.
For differential current measurement, set the orange toggle switch
of the BENNING MA 2-16 to "IPE direct".
Start the IPE test at the appliance tester
(automatic test or manual test).
Follow the instructions shown on the display of the appliance
tester.
Class I, ILeak, with BENNING MA 2-16
Switch position of measuring adapter: IPE
Connection diagram
VDE 0751-1
Circuit diagram
VDE 0751-1
(switch position IPE Δ)
Connect the BENNING MA 2-16 measuring adapter to the
BENNING ST 755/ ST 760 appliance tester according to the
connection conditions.
For differential current measurement, set the orange toggle switch
of the BENNING MA 2-16 to "IPE Δ".
Start the ILeak test at the appliance tester
(automatic test or manual test).
Follow the instructions shown on the display of the appliance
tester.
(IPE Δ)
diff.
67