Advertisement

Class I, RPE
Stationary test sample
Connection diagram
Circuit diagram
 Test the test sample according to the connection diagram.
 Establish a connection between a parallel PE section (e. g. a
shock-proof socket in the same circuit) and the PE socket of the
appliance tester.
 Use the test probe to measure on all accessible conductive parts
of the test sample that are connected to the protective conductor.
Class I, RPE
Stationary test sample
Connection diagram
Circuit diagram
 Test the test sample according to the connection diagram.
 Establish a connection between the PE socket of the appliance
tester and the protective conductor connecting point of the test
sample.
 Use the test probe to measure on all accessible conductive parts
of the test sample that are connected to the protective conductor.
41