36
| Operation
Menu Level 1
Menu Level 2
Functions
Preheater
Functions
Frost protection
Functions
System curve
Functions
Fan control
Fan control
Airflow
Fan control
Airflow unit
Demand control
Menu Level 3
Pre-Heater
Preheater Sp: -30 – 0°C)
P-band: 5°C
Output: Auto(xx%)/ Man
(Off/On)
Frost protection
Alarm limit: 7°C
System curve
EF: 1–10
SF: 1–20
Fan control
Airflow
System curve
%
EF
SF
Airflow l/s
Nom
26
26
High
39
39
Low
14
14
Airflow unit
l/s / m
3
/h / %
Demand control CO2 / RH
Setpoint 0 ppm/0% RH
P-Band 100 ppm/10%RH
I-Time OFF
Explanation
Use this dialog frame to
configure pre-heater function.
Configure the setpoint setting.
Default value is dependant on
system type. In counter flow
units setpoint is not adjustable.
Set the proportional band (P-
band) range for PI controller.
Default value 5°C.
Set output to Auto or Man.
Default setting is Auto. Actual
controller output signal is
presented in auto mode.
Selecting Man, enables the user
to manually control output of the
preheater (On/Off).
Shows current set frost
protection alarm limit in °C for
the installed water coil.
Set Alarm limit in °C.
Default value: 7°C.
This function is to compensate
the flow values for different
system pressures.
See chapter 5.3
Select the type of fan control
you prefer. Fan control by l/s,
m
3
/h or %
Use this dialogue frame to set
the airflow in l/s. The airflow can
be set individually for each fan
EF: Extract fan,
SF: Supply fan
Set the airflow for EF and SF for
each step (Low, Nom, and High.
System curve shall only be
available in case a system with
that type of fan control is used.
Default value: l/s
It is possible control the indoor
air quality using RH (Relative
humidity) or CO2 (Carbon
dioxide) sensor/sensors. Default
setpoint setting is Off. (0%/
0ppm).
Both types should be able to use
at the same time, meaning 2 PI
controllers. When demand
control setpoint is configured,
fans set to auto mode and
regulate against the setpoint.
The fan symbol should have the
middle area empty, and the
outer and inner filled. It should
not be possible to change either.
212962 | v02