Output Phase Failure Detection - Toshiba TOSVERT VF-nC1 Instruction Manual

Industrial inverter (for three-phase inductive motors)
Table of Contents

Advertisement

(An example of terminal assignment) Assigning the trip stop function to the R terminal
Title
Notes:
1) Emergency stop by means of the specified terminal is possible, even when operation is
controlled from the operation panel.
2) If
(DC braking starting frequency) is set to 0.0 (Hz) and
time to 0.0 (sec), the DC braking function will not be activated even if
(emergency DC braking).
2) Emergency stop by means of the operation panel
The emergency stop function can be controlled from the operation panel when the RUN and STOP
keys on the panel are not in use for operation (when they are inoperative).
To activate the emergency stop function, press the STOP key on the operation panel twice.
①Press the STOP key _________ "
Press the STOP key again ____ Operation will be stopped in accordance with the setting of
6.14.4

Output phase failure detection

: Output phase failure detection mode selection
• Function
This parameter allows you to select a mode of detecting an output open-phase failure. If an
open-phase failure persists for one second or more, the tripping function and the FL relay will
be activated, and at the same time, the error message
Set
to " " to open the motor-inverter connection by switching commercial power
operation to inverter operation.
Detection errors may occur for special motors such as high-speed motors.
(Disabled)・・・・・・・・・・・・・・・ No tripping (FL relay not activated)
(Enabled) ・・・・・・・・・・・・・・・ An open-phase check is performed when operation is
(Enabled) ・・・・・・・・・・・・・・・ An open-phase check is performed each time operation
Title
Output open-phase
failure detection mode
selection
6.14.5
Motor 150%-overload time limit
: Motor 150%-overload time limit
• Function
This parameter is used to set the time elapsed before the inverter trips when the motor is
operated under a load of 150%.
Title
Function
Input terminal selection 2 (R)
failure detection signal (FL) will be put out (FL activated).
started for the first time after power has been turned on.
The inverter will trip if an open-phase failure persists for
one second or more. (FL relay activated)
is started. The inverter will trip if an open-phase failure
persists for one second or more. (FL relay activated)
Function
0: Disabled
1: Enabled (Checked at the first
start of operation)
2: Enabled (Checked at each start
of operation)
Function
Motor 150%-overload time
limit
F-23
Adjustment range
0~40, 49, 54~57
" will blink.
. At the same time, " " will be displayed and a
will be displayed.
Adjustment range
Adjustment range
10~800 (sec)
E6581090
Default setting
11
(External trip stop)
(DC braking
is set to 2
6
Default setting
0
Default setting
300