Communication Function (Common Serial - Toshiba TOSVERT VF-nC1 Instruction Manual

Industrial inverter (for three-phase inductive motors)
Table of Contents

Advertisement

6.15.3
Changing the standard monitoring item
• Function
This parameter is used to change the item displayed when the power is turned on.
☆When the power is turned on, the operation frequency is displayed by default like this:
"
" or "
case, however, no prefixes (such as
■Parameter settings
Title
6
6.16

Communication function (common serial)

For details, refer to the Communications Equipment User's Manual.
• Function
The VF-nC1 series of inverters can be connected to a host computer, controller, and so on
(referred to as the computer) via RS232C or RS485 conversion units, so that they can be
operated on a network.
<Computer linking function>
Data is exchanged between an inverter and a computer.
①Monitoring the inverter's operation status (such as output frequency, current and voltage)
②Commands to the inverter (such as RUN and STOP commands)
③Reading, changing and writing inverter parameter settings
<RS232C communications>
Data is exchanged between one inverter and one computer.
<RS485C communications>
Data is exchanged between one computer and multiple inverters (a maximum of 64, or 63 for
binary codes)
☆The following unit and cables are optionally available for common serial communications.
• RS232C conversion unit (Model: RS2001Z)
Communications cable (Model: CAB0011 (1m), CAB0013 (3m), CAB0015 (5m))
• Cable with a built-in RS232C conversion unit (Model: 20035)
• RS485C conversion unit with a terminal board (Model: RS4001Z, RS4002Z)
• Communications cable (Model: CAB0011 (1m), CAB0013 (3m), CAB0015 (5m))
Note: Use a cable 5 m or less in length to connect an inverter and an optional common serial unit.
  
: Selection of monitor display selection
". You can change this default monitoring item, using
Function
Selection of
0: Operation frequency (Hz/free unit)
monitor display
1: Frequency command (Hz/free unit)
selection
2: Output current (%/A)
: Communication baud rate
: Parity
: Inverter number
: Communication error trip time
and
) will be displayed.
Adjustment range
F-28
E6581090
. In that
Default setting
0