6.14.2

Mounting/disassembly of motor starters

Procedure
Protection against electrostatic charge
When handling and installing the SIMATIC ET 200SP motor starter, ensure protection
against electrostatic charging of the components. Changes to the system configuration and
wiring are only permissible after disconnection from the power supply.
To assemble a SIMATIC ET 200SP motor starter, proceed as follows:
● Position the mechanical interlock of the SIMATIC ET 200SP motor starter in the
assembly/disassembly position
● Place the SIMATIC ET 200SP motor starter onto the BaseUnit.
● Turn the mechanical interlock clockwise to the parking position
● Turn the mechanical interlock counterclockwise to the operating position (= end
position)
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
CAUTION
6.14 Mounting/disassembly of motor starters
Wiring
119