Advertisement

Note
Failure of downstream stations is possible
Downstream stations on a bus segment can fail when the factory settings are restored on an
interface module.
Note
Behavior of the installed I/O modules during reset to factory settings
The I/O modules of the ET 200SP distributed I/O system assume the unconfigured state
after a reset to factory settings. The interface module does not acquire any input data and
does not output any output data.
Reference
You will find more information on the procedure in the STEP 7 online help.
12.7.3
Resetting the interface module (PROFINET IO) to factory settings with a
RESET button
Requirement
The supply voltage to the interface module is turned on.
Required tools
3 to 3.5 mm screwdriver (for resetting with a RESET button)
Procedure
Proceed as follows to reset an interface module to factory settings by means of the RESET

button:

1. Remove the interface module from the mounting rail (see Mounting the CPU/interface
module (Page 69)) and swivel it downwards.
2. The RESET button is located on the rear of the interface module behind a small opening:
Press a screwdriver into the small opening for at least 3 seconds to activate the RESET
button.
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
12.7 Resetting CPU/interface module (PROFINET) to factory settings
Maintenance
253