Commissioning procedure
For commissioning of the ET 200SP distributed I/O system as an I-device on the
PROFINET IO, we recommend the following procedure:
Table 11- 2
Step
1
2
3
4
5
6
7
8
9
10
11
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
Procedure for commissioning the ET 200SP as an I-device on the PROFINET IO
Procedure
Installing ET 200SP
Connecting ET 200SP
Supply voltages
PROFINET IO
Sensors and actuators
Inserting a SIMATIC memory card in the I-
device
Configuring the I-device
Checking the protective measures
Switching on supply voltages for the IO
controller
Switching on supply voltages for I-device
and IO devices
Download configuration to the I-device
Switching IO controller and I-device to RUN
mode
Checking LEDs
Testing inputs and outputs
11.2 Commissioning the ET 200SP for PROFINET IO
See ...
Section Installation (Page 63)
Section Wiring (Page 86)
Section Removing/inserting a SIMATIC
memory card on the CPU (Page 205)
Section Configuring (Page 131)
-
Documentation of the IO controller
CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
and documentation of the IO devices
STEP 7 online help
Documentation of the IO controller and
CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
The following functions are helpful: Mon-
itoring and modifying tags, testing with
program status, forcing, controlling the
outputs. See section Test and service
functions (Page 258)