Troubleshooting Guide
Checking Modbus RTU, RS485 communication
5.
6.
7.
5 - 10
-
M/S: Master or slave
-
Number: slave ID
A properly working Modbus communication link should exhibit increasing
numbers of messages sent and received, without a significant increase in errors
or timeouts.
In case of significant errors or timeouts, check the following aspects:
-
That the RS485 cable is correctly, physical connected
-
Transmission characteristics are configured correctly
-
The Modbus Master-Slave pair address is entered correctly
-
RS485 termination is done correctly
This process of checking Modbus communication can be repeated, as required
during the installation/test to confirm communications activity or the lack of it.