9.4.3. Temperature set point adaptation vs. outdoor temperature
Constant supply air T°C with
outdoor T°C compensation
Compensation curve
The supply set point is then
adapted with respect to this
curve. At any time, from the
main screen you can manu-
ally change the supply tem-
perature (range of +/-3ºC).
9.4.4. Automatic control mode
Depending on the temperatures the controller select the most suitable temperature con-
trol mode, between "Supply temperature control with compensation for outdoor tempe-
rature" and "Room temperature control".
9.5. INITIAL TEMPERATURE SETPOINT
To set the setpoint temperature to maintain, keep the following secuence:
Once selected the setpoint temperature.
Controller operation is similar to fi rst case. In this case,
main difference is defi ning a compensation curve defi ned
Heating mode
from factory with 8 set points instead of fi xing a single tem-
perature set point.