COP parameter settings mode
Access to the simplifi ed parameter setting menu (via the password 1111) allows:
• The selection of Normal fl ow and Reduced fl ow of each fan.
• The scaling factor in case one fan is slaved.
• The night set point value of the fans.
The choice between normal or reduced airfl ow can be performed:
• manually
• automatically with programme schedule (see section Time programming)
• remotely, by external digital contact (see section stop-start remote)
A third set point, the "night speed", may be entered via the control panel. The value in % cor-
responds to the percentage of the fan's maximum capacity; it will be used during the night for
free cooling (see corresponding function).
The selection of COP mode in this installer menu automatically confi gures the screen of the
user menu. The user can then change the unit's operation without touching the settings.