19.1. BACNET TCP/IP

The PRO-REG controler has a RJ45 conector that allows the connec-
tion to TCP/IP Bacnet. To enable the functionality, it is necessary to
confi gure the IP direction of the unit and activate the BACnet IP function
with the help of E-Tool program (downloaded from the following
URL: http://www.regincontrols.com/Root/Documentations/42_105786/
CorrigoEVentilation%203.4-1-24.zip
It is necessary to provide the names, fi xed IP's, subnet mask and net-
work interface of each unit to be connected to the same network.
If you need to integrate your CADB / T-HE PRO-REG into a BACNET
system, request our communication manual where appear the technical specifi cations and list of avai-
lable records.

20. REPLACEMENT OF THE BATTERY FROM THE CORRIGO PROGRAMMABLE LOGIC CONTROLLER

When the "battery low" alarm appears and the red indicator light is lit, it means that the backup battery
to save the memory and the real time clock is too low. The procedure to change the battery is described
below. A capacitor allows backing up the memory and running the clock for approximately 10 minutes
after the power is switched off. If the battery can be changed in less than 10 minutes, the program does
not have to be reloaded and the clock will continue to run normally.
The spare battery is type CR2032.
• Using a small screwdriver, pry up the
clips on each side of the case to release
the cover from the base.
• Hold the base and remove the cover.
• Grasp the battery and pull up gently until
the battery exits from its holder.
• Replace the battery with a new. Warning: be sure to respect the polarity when inserting the battery.