Measuring inputs

Current measurement
NOTICE
AC current measurement only.
The device is not suitable for measuring DC current.
PAC3200T is designed for:
• Measuring current of 5 A for connecting standard current transformers. Each current
measuring input can take a continuous load of 10 A. A momentary overcurrent of up to
100 A and a duration of 1 s is possible.
The powerconfig configuration software enables the current direction to be changed
individually for each phase. It is not necessary to change the terminal connections of the
current transformers in the event of connection errors.
Voltage measurement
NOTICE
AC voltage measurement only.
The device is not suitable for measuring DC voltage.
PAC3200T is designed for:
• Direct measurement on the system or using voltage transformers. External voltage
transformers are required to measure higher voltages than the permissible rated input
voltages.
• Measurement voltage up to 277 V / 480 V. The device is designed for measuring input
voltages up to 277 V to the neutral conductor and for measuring input voltages up to
480 V to the external conductor.
Equipment Manual, 09/2022, L1V30415168B-03
Description
2.2 Measuring inputs
15