Modbus command parameters

Addressing the command parameters
You can use Modbus function code 0x06 on the command parameters.
Table A- 13
Command parameters
Offset
Number of
Name
registers
60000
1
Reset the device to the factory set-
tings
60001
1
Device reset (without changing the
Modbus address)
60002
1
Reset maximum values
60003
1
Reset minimum values
60004
1
Reset energy counters
60005
1
Synchronization of the demand
period
60006
1
Tariff switchover
60007
1
Acknowledge the diagnostics bits
(cf. stored bits in unsigned long
beginning offset 205)
60008
1
Switch outputs (if parameterized)
138
Unit
Format
Unsigned
short
Unsigned
short
Unsigned
short
Unsigned
short
Unsigned
short
min
Unsigned
short
Unsigned
short
Unsigned
1)
short
Unsigned
short
Equipment Manual, 10/2019, L1V30425208F-01
Value range
0
0
0 =
all
1 =
Active energy
import tariff 1
2 =
Active energy
import tariff 2
3 =
Active energy
export tariff 1
4 =
Active energy
export tariff 2
5 =
Reactive energy
import tariff 1
6 =
Reactive energy
import tariff 2
7 =
Reactive energy
export tariff 1
8 =
Reactive energy
export tariff 2
9 =
Apparent ener-
gy tariff 1
10 =
Apparent ener-
gy tariff 2
1 ... 60
0 = On-peak
1 = Off-peak
0 ... ffffh
0ffh ... 1ffh
Byte0 0 =
Output 0.0
PAC3120 and PAC3220
Access
W
W
W
W
W
W
W
W
W