Appendix
A.1 Modbus TCP
A.1.4

Modbus-measured variables with function code "0x14"

Addressing the measured variables
The measured variables listed below can be read out via Modbus function code 0x14 "Read
File Record" in two steps.
Step 1 (File Number 1), preset to 10 s
Step 2 (File Number 2), preset to 15 min
Note
Error in the case of inconsistent access to measured values
Please ensure the start offset of the register is correct when making read accesses.
Please ensure the start offset and the number of registers are correct when making write
accesses.
Example: If a value consists of two registers, a read command applied in the second register
will generate an error code. The PAC2200 will also output an error code if a write operation
ends in the middle of a multi-register value.
Abbr. in the "Access"
column
R
W
RW
Offset
Number
Name
of regis-
ters
1
2
Time stamp
3
2
Flags
5
2
Voltage L1 - N
7
2
Voltage L2 - N
9
2
Voltage L3 - N
11
2
Voltage L1 - L2
13
2
Voltage L2 - L3
15
2
Voltage L3 - L1
17
2
Current L1
19
2
Current L2
21
2
Current L3
23
2
Apparent power L1
92
Abbreviations
Read access
Write access
Read and write access
Format
unix_ts
uint32_t
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Unit
Value range
-
-
0= UNFLAGGED
1= FLAGGED
2= SAG
4= SWELL
8= POWER FAIL
V
V
V
V
V
V
A
A
A
VA
Manual, 05/2018, L1V30415167B-02
Access
R
R
R
R
R
R
R
R
R
R
R
R
PAC2200