Dislocation Error Of Compressor Sump Temperature (Oil Temperature) Sensor - Samsung AM017HN1DEH/EU Service Manual

System
Hide thumbs Also See for AM017HN1DEH/EU:
Table of Contents

Advertisement

Troubleshooting
4-4-46

: Dislocation error of Compressor SUMP Temperature (oil temperature) Sensor

Outdoor unit display
×(Operation) ◑(Timer) ◑(Fan) ◑(Filter) ×(Defrost)
Indoor unit display
Criteria
• Refer to how to determine below
Cause of problem
• Sump (oil) temperature sensor dislocation error
1. How to diagnose
1) If the Sump temperature right before the start of compressor = Tsump.ini, current compressor's SUMP temp =Tsump. real,
When the difference between Tsump.ini and Tsump.real is an absolute value so that it cannot be more than 2˚C,
In other words, the condition of Tsump.real-Tsump.ini<2˚C has been satisfied for 60 minutes since a compressor started, it is diag-
nosed as an error.
After 60 minutes of compressor operation, there will be no Sump sensor dislocation detection.
2. How to check
1) Check if a sensor of the relevant compressor has been dislocated in accordance with error code, assemble and correct the error.
370
(digital compressor or fixed compressor 1)
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Am022hn1deh/euAm028fn1deh/euAm022fn1deh/euAm036fn1deh/euAm071jn1deh/euAm056fn2deh/eu ... Show all

Table of Contents