E265 : Dislocation Error Of Compressor Sump Temperature (Oil Temperature) Sensor - Samsung AM009FN1DCH/AA Service Manual

System air conditioner indoor unit
Hide thumbs Also See for AM009FN1DCH/AA:
Table of Contents

Advertisement

Troubleshooting
4-4-44
: Dislocation error of Compressor SUMP Temperature (oil temperature) Sensor
Outdoor unit display
Indoor unit display
Criteria
Cause of problem
1. How to diagnose
1) If the Sump temperature right before the start of compressor = Tsump.ini, current compressor's SUMP temp =Tsump. real,
When the difference between Tsump.ini and Tsump.real is an absolute value so that it cannot be more than 2˚C,
In other words, the condition of Tsump.real-Tsump.ini<2˚C has been satisfied for 60 minutes since a compressor started, it is diag-
nosed as an error.
After 60 minutes of compressor operation, there will be no Sump sensor dislocation detection.
2. How to check
1) Check if a sensor of the relevant compressor has been dislocated in accordance with error code, assemble and correct the error.
4-70
(digital compressor or fixed compressor 1)
×(Operation)
(Timer)
(Fan)
Refer to how to determine below
Sump (oil) temperature sensor dislocation error
(Filter) ×(Defrost)
Samsung Electronics