4-4-2 Main PCB has no power phenomenon
Outdoor unit display
Main PCB has no power phenomenon (7-seg does not blink)
Judgment Method
Hub PCB power and connection wire to detect.
∙ HUB PCB connector wire defects and the connection is not.
∙ Main PCB defective.
Cause of problem
∙ Hub PCB defective.
∙ High pressure switch operation
1. Cause of problem
Is a high pressure switch normal?
HUB PCB CN70 AC220V is connected?
Confirm a blinking of Hub PCB LED.
the connection status of the Main / Hub connection
Replace Fan PCB
Samsung Electronics
Power On
Yes
Yes
Yes
Yes
Did you check
wire?
Yes
No
Refrigerant overcharge?
High pressure switch is defective.
No
Check the connection status of EMI PCB.
Check the short circuit of EMI PCB Fuse.
No
Check the short circuit of Hub PCB.
No
Connecting the communication wire. (CN96)
Troubleshooting
Replace Hub PCB
327