Dc Link Voltage Sensor Error - Samsung AM017HN1DEH/EU Service Manual

System
Hide thumbs Also See for AM017HN1DEH/EU:
Table of Contents

Advertisement

Troubleshooting

4-4-79 DC Link voltage sensor error

Outdoor unit display
Judgment Method
∙ DC voltage detection : Judged as an error if the detected value is more than 2.8V or 0.2V less than
∙ Input voltage defective
∙ AC Power wiring error
Cause of problem
∙ Momentary Overvoltage / Low voltage occurs
∙ PCB voltage sensing circuit defective
1. Cause of problem
Is Power connection accurately connected?
Is Reactor accurately connected?
Is EMI PCB and Inverter PCB
Fan PCB DC-Link voltage connection wire
The case of E396, E498
402
(INVERTER1 PCB)
(OUTDOOR FAN 1 PCB)
Power Off
Yes
Yes
Did the Fuse is short?
No
accurately connected?
Yes
Is Inverter PCB and
accurately connected?
Yes
Replace Inverter PCB
(INVERTER2 PCB)
(OUTDOOR FAN 2 PCB)
No
Power Cable re-connection
No
Check the Reactor connection
Yes
No
Power Off and then re-connection
The case of E396, E498
No
Replace Fuse
Replace Fan PCB
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Am022hn1deh/euAm028fn1deh/euAm022fn1deh/euAm036fn1deh/euAm071jn1deh/euAm056fn2deh/eu ... Show all